MEAN WELL

MPD-45

SWITCHING POWER SUPPLY

SERIES

ISO-9001 CERTIFIED MANUFACTURER

.LOW COST, HIGH RELIABILITY

.COMPACT SIZE, LIGHT WEIGHT

.105ºC OUTPUT CAPACITOR

.100% FULL LOAD BURN-IN TEST

.INTERNATIONAL AC INPUT RANGE

.BUILT IN EMI FILTER, LOW RIPPLE NOISE

.HIGH EFFICIENCY, LOW WORKING TEMPERATURE

.SOFT-START CIRCUIT, LIMITING AC SURGE CURRENT

.SHORT CIRCUIT, OVERLOAD, OVER VOLTAGE PROTECTED

MODEL

MPD-45A

MPD-45B

SPECIFICATION

CH1

CH2

CH1

CH2

DC OUTPUT VOLTAGE

5V

12V

5V

24V

OUTPUT V. TOLERANCE

±4%

±7%

±4%

±7%

OUTPUT RATED CURRENT

3.2A

2A

3.2A

1.2A

OUTPUT MIN. CURRENT

0.4A

0.2A

0.4A

0.2A

OUTPUT MAX. CURRENT

5A

2.5A

5A

1.8A

RIPPLE & NOISE

60mVp-p

120mVp-p

60mVp-p

150mVp-p

LINE REGULATION

±1%

±2%

±1%

±2%

LOAD REGULATION

±3%

±4%

±3%

±4%

RATED OUTPUT POWER

40W

44.8W

MAXIMUM OUTPUT POWER

52W WITH 18 CFM MIN. FORCED AIR CONVECTION

EFFICIENCY

76%

78%

DC VOLTAGE ADJ.

CH1:±10%

CH1:±10%

INPUT VOLTAGE RANGE

90~264VAC 47~440Hz ; 127~370VDC

AC CURRENT

1.2A/115V 0.7A/230V

INRUSH CURRENT

COLD START 20A/115V

40A/230V

LEAKAGE CURRENT

<0.3mA/264VAC

53~75W OUTPUT POWER TYPE:PLUSING HICCUP SHUTDOWN

OVERLOAD PROTECTION

RESET:AUTO RECOVERY

OVER VOLTAGE PROTECTION

5.75~6.75VDC ON CH1

TEMP. COEFFICIENT

±0.04% / ºC (0~50ºC) ON +5V OUTPUT

SETUP, RISE, HOLD UP TIME

800ms, 20ms, 20ms/230VAC

800ms, 20ms, 12ms/115VAC

VIBRATION

10~500Hz, 2G 10min./1cycle, PERIOD FOR 60min. EACH AXES

WITHSTAND VOLTAGE

I/P-O/P:4KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC

ISOLATION RESISTANCE

I/P-O/P, I/P-FG, O/P-FG:500VDC / 100M Ohms

WORKING TEMP., HUMIDITY

-10ºC~+60ºC(REFER TO OUTPUT DERATING CURVE), 20%~90% RH

STORAGE TEMP., HUMIDITY

-20ºC~+85ºC, 10%~95% RH

DIMENSION

127*76.2*30mm (L*W*H) PCB ONLY

WEIGHT

0.23Kgs

SAFETY STANDARDS

UL2601-1, EN6060-1 APPROVED

CISPR11 (EN55011), IEC61000-4-2,3,4,5,6,8,11 IEC61000-3-2,3

EMC STANDARDS

EN60601-1-2 VERIFICATION

NOTE : 1.ALL PARAMETERS ARE SPECIFIED AT 230VAC INPUT, RATED LOAD, 25ºC 70% RH. AMBIENT.

2.TOLERANCE GINCLUDE SET UP TOLERANCE, LINE REGULATION, LOAD REGULATION.

3.RIPPLE & NOISE ARE MEASURED AT 20MHz BY USING A 12" TWISTED PAIR TERMINATED WITH A 0.1uF & 47uF CAPACITOR.

4.LINE REGULATION IS MEASURED FROM LOW LINE TO HIGH LINE AT RATED LOAD.

5.EACH OUTPUT PROVIDE UP TO MAXIMUM CURRENT, BUT TOTAL LOAD CAN NOT EXCEED MAX. OUTPUT POWER.