Файл: Исследование суточных вариаций поровой активности радона в поверхностных грунтах удк 550. 42 546. 296 551. 51.docx

ВУЗ: Не указан

Категория: Не указан

Дисциплина: Не указана

Добавлен: 30.10.2023

Просмотров: 265

Скачиваний: 2

ВНИМАНИЕ! Если данный файл нарушает Ваши авторские права, то обязательно сообщите нам.

СОДЕРЖАНИЕ

PLANNED RESULTS OF THE DEVELOPMENT OF THE PLO/OPOP

SYMBOLS AND ABBREVIATIONS

Introduction

1 Chapter

Areas applications quantities density flow radon

Climatology. Radon - as a tracer of air exchangeprocesses

Static and dynamic methods measurements

Chapter

Dynamics of radon activity and its decay products inside the storage chamber

Conclusion on the chapter The field of β-radiation at depths of 0.5 and 1 m quite well reflects the dynamics of the radon subsoil field, the daily variation is well traced. However, the daily course of the β-field in some periods has a shift compared to the daily course of the radon field, i.e. the time of the onset of the maximum in the dynamics of the β-field is ahead/late by several hours.The dynamics of RA of radon in soil air at the same depth, but at a distance of 1.5–2 m, can differ significantly. The maxima in the daily course of RA of radon at different depths occur at different times, at a depth of 0.5 m - approximately at 16-18 hours, and at a depth of 1 m - at 24 hours. The delay in some periods reaches 8 hours.Correlation analysis between the radon field and meteorological values revealed only a significant relationship with the amount of rainfall.A 2-month experiment on the calibration of β- and α-radiation detectors installed in wells did not make it possible to unambiguously determine the correction factors for converting to units of volumetric activity. As a result, it was decided to conduct a second experiment with some adjustment of the experimental design, as well as refinement of the VA detector installation scheme. The requirements for the conditions for calibrating the readings of the VA detector in units of RA of radon are as follows: Wells with VA detectors installed inside should not be opened during calibration, i.e. tubes for pumping air from the well, which are cyclically connected to the radon radiometer, should be installed at least a day before the start of the experiment. The VA detectors should not be removed from the well or moved in the well during calibration, as this leads to a distortion of the time series of data. To calculate the coefficient of decrease in the range of diurnal variations after the start of pumping air from the well, it is necessary to record data from the VA detector at least a week before the start of the experiment, and after its completion. The development of the project infrastructure made it possible to analyze the results of the calibration of soil detectors by 0.5 and 1 мusing a radon radiometer, which showed the following:at depth, 0,5 мthe temporal changes in the α- and β-fields are practically synchronous, but have different amplitudes ;in the daily course of radon VA at different depths, the maxima at depth 0,5 мare recorded at 16–18 h, and at depth 1 мat 24 h; the delay in time of the moments of the onset of maxima in radon VA is

Chapter 4 Financial management, resource efficiency and resource saving

Consumer portrait

SWOT analysis

Project Initiation

Project Participants

Project Schedule

Scientific and technical research budget

Basic salary

Additional salary

Overhead costs

Conclusion

Social responsibility

Industrial safety

Artificial lighting

Electrical safety

Static electricity

Safety in emergencies

Conclusions to the section social security

List of sources used

application 1


Acceptable microclimatic conditions do not cause damage or health disorders, but can lead to general and local sensations of thermal

discomfort, tension in thermoregulation mechanisms, deterioration of well-being and decreased performance.

To select a suitable exhaust fan for room 123 of housing 10 with an area of 25 m3, we use the following formula

???? = ???? ????

Where L is the fan capacity, m3/hour; S is the area of the room, m2; h - ceiling height, m; k is the rate of air exchange, then we get:

???? = 25 3 2 = 150 m3/hour

Fan "Event 150C" is able to provide the required air extraction performance for a given room. [90].

Table 5.4 Fan specifications of “Event 150С”.


Type of instalation:

wall

Channel type:

circular

Voltage:

220 V

Power (W)

22

Efficiency:

320 m³/h

Number of speeds:

1

Duct diameter:

150 mm


In room 123 of building 10, all microclimate standards are met in accordance with SanPiN 2.2.4.548-96.

      1. 1   ...   24   25   26   27   28   29   30   31   32

Artificial lighting


Artificial lighting is divided into working, emergency, security and duty.

The standardized characteristics of indoor and outdoor lighting are provided both by general lighting fixtures and by their joint action with emergency lighting fixtures.

Work lighting should be provided for all premises of buildings, as well as for areas of open spaces intended for work, the passage of people and traffic. For rooms with zones with different natural lighting conditions and different operating modes, separate control of the lighting of such zones is necessary.

Standard lighting indicators for office premises are shown in Table 5.4.

Table 5.3 - Standard lighting indicators for the main premises of public, residential and auxiliary buildings.




The plane of

Category and sub-category of visual work

Artificial lighting




normalizatio n of

illumination

Illumination of working surfaces, lx

UGR combined discomfort score,

no more

Illumination ripple coefficient,

Light source color rendering index Ra

Premises

and KEO,

the height of the plane

With the combi

ned

In gener al




above the










floor, m







Cabinets and work rooms, offices, representative

offices

G-0,8

B-1

400/200

300

21

15

80


The total illumination in a room with personal computers should be 300 lux.

As sources of artificial lighting at the workplace, 4 office LED lamps are used, the location of which is shown in Figure 5.1.



Figure 5.1 - Layout of fixtures at the workplace of a lighting engineer: 1- fixtures.
Let's calculate the artificial illumination of the room using the utilization factor method. The characteristics of the LED luminaire used in office space are as follows:

  • power 40 W;

  • luminous flux 4240 lm;

  • light temperature 4000 K;

- IP 40.

i A B

h ( A B)
where: A is the length of the room, m; B is the width of the room, m; h is the height of the luminaire suspension above the working surface, m.

i A B

h ( A B)

6 4

2 (6 4)

1,2


The reflection coefficient of the walls is taken ρ = 50%.

According to SP 52.13330.2016, the minimum illumination on the working surface must be at least Emin = 300 lux.

Let's calculate the luminous flux of the lamp. There are 4 lighting devices in the room, N = 2; safety factor of LED luminaires k = 1.1; the numerical ratio of uneven illumination z = 1; the index of the room determines the utilization factor of the luminous flux, ƞ = 0.51. Then the luminous flux is:

???? ???? ???? ????

Ф =

???? ƞ

300 1,1 24 1

=

4 0,51
= 3882 ????????

We compare the calculated value of the luminous flux with the value of the selected light fixture, 4240 lm.

Фстанд. − Фрасч.

−10
−10

Фстанд.

4240 3882


4240

  • 100% 20




  • 100% 20


−10 8.44 20

We get that the luminous flux of the selected lighting device is suitable for lighting rooms where computers with an illumination of 300 lux are installed.

Many types of industrial and scientific activities are characterized by an increased load on the visual system and attention processes. In combination with physical inactivity, neuro-emotional stress, long-term preservation of a non-optimal basic working posture leads to the development of visual and general fatigue and a decrease in working capacity.

In the prevention of general and visual fatigue in representatives of a number of professions, an important role belongs to the provision of visual comfort. This includes general illumination, room color, light distribution, etc. The optimal location of objects of the labor process at a distance of 30-100 cm from the eyes.

When working for a long time at a personal computer, regulated breaks during which gymnastics is performed must be taken into account. It consists of general strengthening and special exercises for the eyes. The latter should be based on the principles of training and relaxation of accommodation, as well as manipulations that improve the blood supply to the eyes.

Also, correctly designed and executed lighting ensures a high level of efficiency, reduces the load on the organs of vision, has a positive psychological effect on workers, and helps to increase labor productivity.

      1. 1   ...   24   25   26   27   28   29   30   31   32

Electrical safety


Electrical safety is a system of organizational and technical measures and means to protect people from harmful and dangerous effects of electric current, electric arc, electromagnetic field and static electricity.

The premises for electrical safety are divided into 3 groups:

        1. A room without increased danger (dry, well-heated, room with non-conductive floors, with a temperature of 18–20 °, with a humidity of 40–50%).

        2. A room with increased danger (where there is one of the following signs: high temperature, humidity 70-80%, conductive floors, metal dust, the presence of grounding, a large amount of equipment).

        3. Premises are especially dangerous, in which there are two signs from the second group or there are caustic or poisonous explosive substances in the room.

According to [75], electrical safety must be ensured by the design of electrical installations, technical methods and means of protection. Electrical installations and their parts are designed in such a way that workers are not exposed to dangerous and harmful effects of electric current and electromagnetic fields, and comply with electrical safety requirements.

First of all, safety is ensured by the use of collective protective equipment, and then, if it cannot be ensured, personal protective equipment is used.

The means of collective protection against electric shock include: protective devices, which can be stationary and portable. Fences can be interlocked with devices that cut off the operating voltage when removed; insulating devices and coatings; protective grounding, neutralization and protective shutdown devices; remote control devices; safety devices, etc.

Also, personal protective equipment is divided into basic and additional. The main protective insulating means include insulating rods, insulating pliers and electrical voltage indicators, dielectric gloves, fitting and assembly tools with insulating handles. Additional insulating protective equipment includes means that supplement the main ones, and can also serve to protect against touch voltage and step voltage. Dielectric galoshes, dielectric rugs, insulating supports [76] serve as additional protective equipment.

      1. Noise


Industrial noise is the noise in workplaces, on sites or on the territory of enterprises, which occurs during the production process. Noise and vibration worsen working conditions, have a harmful effect on the human body, namely, on the hearing organs and on the entire body through the central nervous system. As a result, attention is weakened, memory deteriorates, reaction decreases, and the number of