Файл: Исследование суточных вариаций поровой активности радона в поверхностных грунтах удк 550. 42 546. 296 551. 51.docx

ВУЗ: Не указан

Категория: Не указан

Дисциплина: Не указана

Добавлен: 30.10.2023

Просмотров: 279

Скачиваний: 2

ВНИМАНИЕ! Если данный файл нарушает Ваши авторские права, то обязательно сообщите нам.

СОДЕРЖАНИЕ

PLANNED RESULTS OF THE DEVELOPMENT OF THE PLO/OPOP

SYMBOLS AND ABBREVIATIONS

Introduction

1 Chapter

Areas applications quantities density flow radon

Climatology. Radon - as a tracer of air exchangeprocesses

Static and dynamic methods measurements

Chapter

Dynamics of radon activity and its decay products inside the storage chamber

Conclusion on the chapter The field of β-radiation at depths of 0.5 and 1 m quite well reflects the dynamics of the radon subsoil field, the daily variation is well traced. However, the daily course of the β-field in some periods has a shift compared to the daily course of the radon field, i.e. the time of the onset of the maximum in the dynamics of the β-field is ahead/late by several hours.The dynamics of RA of radon in soil air at the same depth, but at a distance of 1.5–2 m, can differ significantly. The maxima in the daily course of RA of radon at different depths occur at different times, at a depth of 0.5 m - approximately at 16-18 hours, and at a depth of 1 m - at 24 hours. The delay in some periods reaches 8 hours.Correlation analysis between the radon field and meteorological values revealed only a significant relationship with the amount of rainfall.A 2-month experiment on the calibration of β- and α-radiation detectors installed in wells did not make it possible to unambiguously determine the correction factors for converting to units of volumetric activity. As a result, it was decided to conduct a second experiment with some adjustment of the experimental design, as well as refinement of the VA detector installation scheme. The requirements for the conditions for calibrating the readings of the VA detector in units of RA of radon are as follows: Wells with VA detectors installed inside should not be opened during calibration, i.e. tubes for pumping air from the well, which are cyclically connected to the radon radiometer, should be installed at least a day before the start of the experiment. The VA detectors should not be removed from the well or moved in the well during calibration, as this leads to a distortion of the time series of data. To calculate the coefficient of decrease in the range of diurnal variations after the start of pumping air from the well, it is necessary to record data from the VA detector at least a week before the start of the experiment, and after its completion. The development of the project infrastructure made it possible to analyze the results of the calibration of soil detectors by 0.5 and 1 мusing a radon radiometer, which showed the following:at depth, 0,5 мthe temporal changes in the α- and β-fields are practically synchronous, but have different amplitudes ;in the daily course of radon VA at different depths, the maxima at depth 0,5 мare recorded at 16–18 h, and at depth 1 мat 24 h; the delay in time of the moments of the onset of maxima in radon VA is

Chapter 4 Financial management, resource efficiency and resource saving

Consumer portrait

SWOT analysis

Project Initiation

Project Participants

Project Schedule

Scientific and technical research budget

Basic salary

Additional salary

Overhead costs

Conclusion

Social responsibility

Industrial safety

Artificial lighting

Electrical safety

Static electricity

Safety in emergencies

Conclusions to the section social security

List of sources used

application 1

errors during work increases. Noise can be generated by operating equipment, air conditioning units, daylight fixtures, and can also be emitted from outside.

In accordance with SanPiN 1.2.3685-21 [77], the standardized indicators in the workplace are:

  • equivalent sound level per work shift;

  • maximum sound level;

  • peak sound level.

The standard equivalent sound level in the workplace is 80 dB. At noise levels above the permissible level, it is necessary to provide RMS and PPE.

Collective protection means [78]:

  • elimination of the causes of noise or its significant attenuation in the source of education;

  • isolation of noise sources from the environment by means of sound vibration isolation, sound and vibration absorption;

  • the use of means that reduce noise and vibration along the path of their propagation.

Personal protective equipment [78]:

  • the use of overalls, footwear and hearing protection: headphones, earplugs, antiphones.



      1. 1   ...   24   25   26   27   28   29   30   31   32

Static electricity


All conductive parts of process equipment and other objects that generate or store static electricity must be grounded, regardless of whether other ESD devices are used. An ESD grounding device must have a maximum resistance of 100 ohms. According to [SanPin 1.2.3685-21] collective protection means against static electricity are: anti-electrostatic substances, humidifying devices, neutralizers, shielding substances. Anti-static footwear, gowns, and anti-electrostatic hand protection should be used as personal protective equipment.

    1. Fire and explosion safety


Depending on the characteristics of substances and materials in the room, according to the explosion and fire hazard, the premises are subdivided into categories A, B, C, D and F in accordance with [86].

The room in question belongs to category C, since it contains solid combustible substances in a cold state. Possible causes of fire:

  • work with open electrical equipment;

  • short circuits in power supplies;

  • non-observance of fire safety rules.

In order to reduce the risk of fire and minimize possible damage, preventive measures are taken, which are subdivided into organizational, technical, operational and regime. Organizational and technical measures consist in conducting regular briefings of employees responsible for fire safety, training employees in the proper operation of equipment and the necessary actions in the event of a fire, certification of substances, materials and products in terms of ensuring fire safety, production and use of visual agitation tools to ensure fire safety [86]. Operational measures include preventive inspections of equipment.

Regime measures include the establishment of rules for organizing work and compliance with fire safety measures. To prevent a fire, the following fire safety rules must be observed:

  • maintenance of premises in accordance with fire safety requirements;

  • proper operation of the equipment (correct connection of equipment to the power supply network, control of equipment heating);

  • training of production personnel in fire safety rules;

  • availability, correct placement and use of fire extinguishing equipment.


In a room with electrical equipment, in order to avoid electric shock, it is advisable to use carbon dioxide or dry powder fire extinguishers. These fire extinguishers are designed to extinguish fires of various substances and materials, electrical installations under

voltages up to 1000 V, flammable liquids. Chemical and foam extinguishers are not permitted.[86] Fire extinguishers should be located at the protected object in accordance with the requirements so that they are protected from direct sunlight, heat flows, mechanical influences and other adverse factors (vibration, aggressive environment, high humidity, etc.). They must be clearly visible and easily accessible in the event of a fire. It is preferable to place fire extinguishers near the places where fire is most likely to occur, along the paths of the passage, as well as near the exit from the premises. Fire extinguishers should not interfere with the evacuation of people during a fire. According to fire safety requirements, there are 2 OP 3 fire extinguishers (portable powder fire extinguishers) on the floor, stairwells are equipped with hydrants, and there is a fire alarm button[86].

    1. 1   ...   24   25   26   27   28   29   30   31   32

Safety in emergencies


Emergency situation - a situation in a certain area resulting from an accident, dangerous natural phenomenon, catastrophe, natural or other disaster that may or have resulted in human casualties, damage to human health or the environment, significant material losses and disruption of the living conditions of people.

The most common emergencies in the building where the bachelor's job was developed are intrusion and fire.

Table 5.5 - Emergency situations, measures to prevent emergencies and eliminate the consequences of an emergency



Emergency

situation

Emergency prevention

measures

Measures to eliminate the consequences

of an emergency


1

Falling from height

  1. Maintenance of the premises in proper order.

  2. Limitation of working space.

  3. Timely briefing.

1. Examine or interview the victim; 2.if necessary -

call an ambulance;

  1. stop bleeding, if any;

  2. if there is a suspicion that the victim has a broken spine (sharp pain in the spine at the slightest movement), it is necessary to provide the victim with complete rest in

the supine position until qualified medical care is provided.

2

corresponding growth

  1. Covering stair steps with anti-slip coating.

  2. Timely briefing.

  1. Call an ambulance;

  2. stop bleeding, if any;

  3. if there is a suspicion that the victim has a broken spine (sharp pain in the spine at the slightest movement), it is necessary to provide the victim with complete rest in the supine position until qualified medical

care is provided.

3

Falling down the stairs

  1. Grounding of all electrical installations.

  2. Limitation of working space.

  3. Ensuring the inaccessibility of live parts of the equipment.

  4. Timely briefing.

  1. Quickly release the victim from the action of the electric current [26];

  2. call an ambulance;

  3. if the victim has lost consciousness, but breathing is preserved, he should be laid down comfortably, unbuttoned tight clothing, create an influx of fresh air and ensure complete rest;

  4. the victim should be allowed to smell ammonia, sprinkle water on his face, rub and warm the body;

  5. In the absence of breathing, artificial

respiration and heart massage should be done immediately.

4

Electric shock

  1. Timely briefing.

  2. Establishment of means of automatic fire extinguishing in premises.

  3. Installation of smoke and fire detectors.

  4. Providing evacuation routes and maintaining them in proper condition.

4. Control of the work of electrical appliances.

  1. De-energize the room, cut off the air supply;

  2. immediately report the fire to the duty officer or to the guard post;

  3. If possible, take measures to evacuate people, extinguish a fire and save material assets.


First case: penetration of unauthorized persons. To ensure the safety of the employee and prevent the entry of unauthorized persons into the enterprise, a number of security measures should be used:

      1. Organize a checkpoint.

      2. Hire a security guard to bypass the building.

      3. Install video surveillance systems in production halls, as well as at all entrances and exits from the building.

      4. Install warning security systems in case of unauthorized entry into the enterprise outside of working hours.

Second case: fire. Possible causes of sunburn:

  • malfunction of current-carrying parts of installations;

  • work with open electrical equipment;

  • short circuits in the power supply;

  • non-observance of fire safety rules;

  • presence of combustible components: documents, doors, tables, cable insulation, etc.

Fire prevention measures are divided into: organizational, technical, operational and regime.

Organizational measures provide for the correct operation of equipment, the correct maintenance of buildings and territories, fire- prevention instructions for workers and employees, training of production personnel in fire safety rules, the publication of instructions, posters, and an evacuation plan.

Technical measures include: compliance with fire regulations, norms in the design of buildings, in the installation of electrical wires and equipment, heating, ventilation, lighting, proper placement of equipment.

Regime measures include the establishment of rules for organizing work, and compliance with fire safety measures. To prevent

a fire from short circuits, overloads, etc., the following fire safety rules must be observed:

  • elimination of the formation of a combustible environment (equipment sealing, air control, working and emergency ventilation);

  • the use of non-combustible or hardly combustible materials in the construction and decoration of buildings; correct operation of equipment (correct connection of equipment to the power supply network, control of equipment heating);

  • correct maintenance of buildings and territories (exclusion of the formation of an ignition source - prevention of spontaneous combustion of substances, limitation of hot work);

  • training of production personnel in fire safety rules;

  • publication of instructions, posters, availability of an evacuation